Using
CT975 Printed Circuit Board
TROUBLE
SHOOTING GUIDE
No
display at topside
|
Check
miss-wire fuse between
J38 and J18 If blown, check
|
|
Incoming
wiring L1, L2, N are correct
|
|
Check
that connection to main board is clean and sound at J30
|
|
Test
a new topside control.
|
|
Check
for 120V primary power going into the transformer and for 12V secondary
power out of the transformer to J35 & J34 on the board before replacing
the transformer.
|
|
Replace
board if there is 12V to J35 & J34
|
|
Display flashes " th1 / 39
" or - - - / 39
on system start up
|
|
If
the fill water is less than 39F it will stay in freeze protect mode until over-ridden
or the water temp rises above 39F
|
(
see freeze protect information )
|
Check
that temperature sensing probe connection to main board
is clean and sound at location J2.
|
|
Try
new temperature sensing probe.
|
Display
fl
ashes " th2 / current
temperature " or - - - / current temperature on
system start up.
|
Check
that the temperature sensing probe connected to the main board is clean and
sound at location J1.
|
|
Try
new temperature sensing probe
|
Display
flashes " th2 / 39 "
or - - - / 39 on
system start up
|
This
indicates that both thermisters
are detecting tub water temperature of less than 39F / 4C or they are both
disconnected (open). Pump(s) and blower will run in this condition.
|
Display flashes " OH "
or the Current Temperature"
( OVER
HEAT )
|
This
indicates that the spa
water temp is over 112F. The system should be shut down in this state and
will re-start automatically when the water cools below 112F.
|
Display flashes " hot
" or the Current
Temperature ( OVER HEAT )
|
This
indicates that the heater body
is over 112F. The system should be shut down in this state and will re-start
automatically when the water cools below 112F.
|
Display flashes " HL
" or Current Temperature
( HIGH LIMIT )
|
This
indicates that either the heater or the spa has reached 118F
or higher. The system will not re-start automatically.
To re-start the system, the water temperature must be below 112F and
the heater key at the topside control must be pressed.
|
Display flashes " HL / 210"
( THERMISTER SHORT )
|
This
indicates that one of the thermisters is shorted out causing a cross
between
the two terminals at J1 or J2.
|
Erratic
operation or 0 at topside panel
|
Check
for proper connection at J30
|
|
Shut
off system and restart
|
|
Check
for debris inside topside panel control housing
|
|
Check
cable connection at the topside control remove, clean reconnect
|
|
Try
new topside control
|
|
Replace
main board
|
No
heat
|
Check
the topside control for " HL". This indicates that the system has
overheated. Make sure the temperature has fallen to less than 112F
and press the heat key or turn the power off and back on again to reset.
|
|
Check
that temperature set point is higher than actual tub temperature.
|
|
Check
for flashing LED at topside control to indicate heat demand
|
|
Check
that filters are clean
|
|
Check
to see if the pilot light at the equipment panel is on. This indicates if
power is actually getting to the heater element. If this light is on and
there is still no heat, the element should be checked for continuity. If the
element is open, it needs to be replaced.
|
|
If
the pilot light does not turn on, then the pressure switch may need to be
adjusted. The pressure switch is located on the heater body and has a small
wheel on it. This wheel should be turned counter clockwise to allow the
heater to run on less water flow / pressure. This pressure switch is a
protection switch that is meant to turn the heater off if the pump fails to
operate or if there is not enough pump pressure. A test to see if the
pressure switch has been adjusted correctly is to unplug the circulation
pump and see if the heater shuts off. It should operate again when the pump
is plugged back in. The heater should not be allowed to operate under static
(gravitational) pressure when the pump is not on as it will cause an instant
overheat.
|
|
If
a flow switch is used it must be checked for continuity when closed.
|
|
·
Note
: Some systems have fixed pressure switches to prevent tampering.
It is highly recommended that the spa plumbing is checked
for obstructions first.
|
|
If these remedies do not work the power will have to be checked from the
element terminals back to the power source at the main input power terminal.
This must be done with a voltmeter checking for voltage at each connection
from the heater element back through the relays to the main power as a
process of elimination.
|
|
The
power should be checked at the coil side of the relay. If there is power at
the coil side of the relay and the relay is not closed (allowing power to
pass through the power terminals), and then the relay must be replaced.
|
Temperature
readout is wrong
|
Remove
temperature sensor / thermister from the tub location and submerge it
directly into the water. This will verify if the sensor has been installed
where ambient air has affected it or it is defective.
|
Overheat
|
If
the water is too hot and the high limit has tripped, the water must be
allowed to drop to less than 112F before it will reset. Reset by pressing
the heat key at the topside control or restarting the system.
|
|
The
circulation of the water may be too low, allowing the heater body to
overheat. Be sure that all valves are fully open to allow maximum water flow
over the heater element and that there are no flow obstructions.
|
|
If
the LED at the topside panel is not flashing and the spa is still heating,
then the heater relays may be welded shut. This can be checked by making
sure that the temperature set point is lower than the actual spa temperature
and then checking that there is no power going to the coil side of the
relay. If there is no power at the coil and there is power passing through
the relay power terminals, then you know it is welded shut. A further test to
this is to tap the relay to see if the internal " tack weld " frees
up. In the event that there is not a replacement relay readily available,
this may work temporally until a new relay can be installed.
|
|
The
friction and radiant heat from the pump motor
can cause an extremely high ambient temperature around the spa and the
equipment causing an overheat condition. If this condition is suspect, try
running the spa with the equipment door off to see if it still overheats.
Some software will shut the low speed pump off if the temperature creeps 2
degrees F above the set point. This will not affect a circ pump.
|
Pump(s),
Blower or light does not shut off
|
System
may be in freeze protect mode
if water is less than 52F
|
(
this temp level may vary with custom software ) System will run in
protection mode and you will not be able to control pumps, heater
or optional blower. You must introduce warm water into spa or manually over-ride
the system or wait for the system to heat up on its own. Depending on outdoor
temp this can take several hours.
|
Try
new topside control
|
|
Replace
main board
|
Circulation
pump does not work
|
Check
the fuse and power connections.
|
|
Circ
pumps are not powered through the circuit board and will remain on in board
power or internal board failure to prevent possible freezing.
|
Light
does not work
|
Check
bulb
|
|
Check
for 120V into transformer and 12V out to light
|
|
Check
topside control for light function
|
Filter cycle does not operate
|
Adjust
the temperature set point to be within 2
degrees F of the actual water temperature. If the water
temperature creep 2 degrees F higher than the set temp, the system will shut
off to allow the water to cool. When the water cools down to the desired set
point, filtration will resume. Proper ventilation of the equipment will
minimize this.
|
Ground
Fault Interrupter Trips
|
Check
if it does it only when heat turns on, if so check element by removing the
power to the element terminal and turn the heat on. If it only faults when
the element is connected with power, the element has a ground fault and must
be replaced.
|
|
Check
the element for possible leak or condensation at bulkhead.
|
|
This
test can be done with the pump(s), blower, ozonator, or any other peripheral
equipment as a process of elimination to see where the fault may be.
|
|
Be
sure that the neutral on the GFCI has been wired properly in the main panel.
|
General
|
All
connections should be checked that they are secure. |
|
Always
exercise general electrical common sense for safety. |
Please
do not hesitate to contact us if you have any questions or concerns.
Correct-Tech,
Inc.
|